TR-PULL-SA-TRIGA (TRIGA)
Addressable Single Action and Dual Action Pull Stations
(TR-PULL-SA / TR-PULL-DA)
Product Overview
The TR-PULL-SA (Single Action) and TR-PULL-DA
(Dual Action) Pull Stations are high-performance, addressable manual fire alarm
devices designed for use with Triga Series Fire Alarm Control Panels (FACPs).
Built for reliability and durability, these pull stations provide a quick and
easy method to manually initiate a fire alarm signal in case of an emergency.
- Single
Action (TR-PULL-SA): Requires one motion to activate.
- Dual
Action (TR-PULL-DA): Requires two motions to activate for added
protection against accidental alarms.
Key Features
- Durable
construction with high-quality materials for long-term performance.
- Clear,
easy-to-read labeling for fast identification during emergencies.
- Addressable
design ensures precise identification of activation point on the
control panel.
- Compatible
with Triga Fire Alarm Systems for seamless integration.
- Surface
or semi-flush mounting options for flexible installation.
- Optional
trim ring available for semi-flush mounting applications.
- Easy
installation and maintenance.
- Meets
international fire safety and building code requirements.
Installation Options
The TR-PULL-SA and TR-PULL-DA can be:
- Surface
mounted using an SB-I/O surface back box, or
- Semi-flush
mounted on:
- Standard
single-gang box (minimum depth: 2.13" / 5.40 cm)
- Double-gang
or 4" (10.61 cm) square electrical box
- Optional
trim ring available for semi-flush mounting aesthetics
System Compatibility
Both pull stations are fully compatible with the following Triga
Series Fire Alarm Control Panels (FACPs):
- TR-2100R
/ TR-2100B
- TR-2100ECSR
/ TR-2100ECSB
- TR-R2100R
/ TR-R2100B
Addressable Single Action & Dual Action Pull Stations
(TR-PULL-SA / TR-PULL-DA)
Product Overview
The TR-PULL-SA (Single Action) and TR-PULL-DA
(Dual Action) Addressable Pull Stations provide a dependable and
user-friendly manual fire alarm interface for emergency activation. Designed
for use with Triga Series Fire Alarm Control Panels (FACPs), these pull
stations combine rugged construction, ease of use, and advanced addressable
communication to ensure reliable operation in any fire safety system.
- Single
Action (TR-PULL-SA): One motion activates the alarm.
- Dual
Action (TR-PULL-DA): Two motions required for activation, preventing
accidental alarms.
Built from durable LEXAN® materials and compliant
with ADA accessibility standards, these pull stations are engineered for
long-lasting performance and maximum safety.
Key Features
- Non-alarm
maintenance access: Installer can open the station for service without
triggering an alarm condition.
- Dual-color
status LED: Visible through the handle — blinks green for
normal operation, steady red in alarm condition.
- Key-operated
test and reset lock: Ensures secure system testing and reset.
- Lock
compatibility: Uses the same key as the associated Fire Alarm Control
Panel (FACP).
- ADA
compliant: Meets the 5 lbs maximum pull force and ADAAG
Section 4.1.3(13) guidelines for accessibility.
- Durable
LEXAN® construction: Shell, door, and handle molded from high-impact,
fire-resistant materials.
- Reliable
analog communication: Ensures stable and accurate signal transmission.
- Braille-labeled
handle: Enhances accessibility for all users.
- Rotary
address switches: Allow fast and precise device configuration.
- Visible
activation indicator: Handle latches in the down position and displays
the word “Activated” when pulled.
- UL
Listed – including UL 38, Standard for Manually Actuated
Signaling Systems.
Installation
The TR-PULL-SA and TR-PULL-DA can be:
- Surface
mounted using an SB-I/O surface back box, or
- Semi-flush
mounted on:
- Standard
single-gang box (min. depth: 2.13” / 5.40 cm)
- Double-gang
or 4” (10.61 cm) square electrical box
- Optional
trim ring available for semi-flush applications
System Compatibility
Compatible with the following Triga Series Fire Alarm
Control Panels (FACPs):
- TR-2100R
/ TR-2100B
- TR-2100ECSR
/ TR-2100ECSB
- TR-R2100R
/ TR-R2100B
Certifications & Compliance
- UL
38 Listed – Manually Actuated Signaling System
- ADA
Compliant
- LEXAN®
Material Certified for Durability