Triga Horn / Sounder – Technical Specifications
Electrical Specifications
|
Parameter |
Specification |
|
Operating Voltage |
Regulated 16–33 VDC / FWR |
|
RMS Operating Current |
DC: 35 mA |
|
Wire Size |
12–18 AWG |
Sound Level (dBA)
|
Voltage |
Reverberant |
Anechoic |
|
16 V |
80 |
85 |
|
24 V |
82 |
89 |
|
33 V |
85 |
91 |
Directional Characteristics
Horizontal Axis
|
Angle |
OSPL (dBA) |
|
0° (ref) |
0 |
|
±44° |
-3 |
|
±54° |
-6 |
|
±90° |
-10.5 |
Vertical Axis
|
Angle |
OSPL (dBA) |
|
0° (ref) |
0 |
|
±52° |
-3 |
|
±55° |
-6 |
|
±90° |
-12 |
Other Specifications
|
Parameter |
Specification |
|
Operating Temperature |
0°C to 49°C |
|
Operating Humidity |
0 to 93% RH |
|
Horn Pattern |
Temporal 3 |
|
Location |
Indoor wall / ceiling |